Permit Application Status
B-21-745
In order to view fees, you need to be signed in. You will only be able to schedule inspections if you are a contact on the permit application.
Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.
Date Returned | Name |
---|---|
09/02/2021 | arch revision 090121 (Stamped) |
09/02/2021 | archSpec090121 (Stamped) |
12/20/2021 | 211215_KVC_Bulletin_02 (Stamped) |
Review Type | Outcome | Est. Completion Date | Completed |
---|---|---|---|
Fire Code Review | Approved | 01/13/2022 | |
Shannon Yaconiello
|
|||
Ok for CC. | |||
Building Code Review | TCO Approved | 12/24/2021 | 12/21/2021 |
Todd Carr
|
|||
TCO approved with conditions | |||
Building Code Review | TCO Approved | 12/21/2021 | |
Heidi Spengler
|
|||
Miscellaneous
Outstanding
12/21/2021
Needs to pass final inspection
|
|||
Needs to pass final inspection Reviewed addendum 09-01-21 | |||
Planning Review | TCO Approved | 12/24/2021 | 12/21/2021 |
Kelly Douglas, AICP
|
|||
TCO/CO/CC Approval TCO OK - kd 12/21/21 | |||
Fire Code Review | TCO Approved | 12/24/2021 | 12/21/2021 |
Shannon Yaconiello
|
|||
12/20/21 - Ok for TCO but need following for CC: 1. New pull stations in KVC are currently sending alarm signal to panel and monitoring. New pull stations are not triggering notification devices in building and needs that fixed. 2. Add general alarm Horn/Strobe outside southwest entrance to KVC that now has remote annunciator. 3. Reprogram Horn/Strobe over Fire Dept. Connection at southwest corner of building to activate on fire sprinkler flow only. | |||
Finance Department Review | TCO Approved | 12/24/2021 | 12/20/2021 |
Amy Camilletti
|
|||
TCO/CO/CC Approval The City of Steamboat Springs Finance department has approved a TEMPORARY CERTIFICATE on this project. A construction use tax reconciliation must be completed within 90 days to be compliant with the City of Steamboat Springs Municipal Code AND prior to signoff for the FINAL certificate of occupancy/completion with the Routt County Building Department. | |||
External Agencies Review | TCO Approved | 12/20/2021 | |
Todd Carr
|
|||
Routt Environmental Health: TCO approved for childcare rooms and areas, not approved to use commercial kitchen | |||
GIS Land Development Review | Approved | 12/24/2021 | 12/17/2021 |
Heidi Spengler
|
|||
CC approved RCBD | |||
Legacy Permitting Review | Approved w/ Conditions | 08/11/2021 | |
SysAdmin
|
|||
VP legacy plan review: Routt Building sysadmin - Jun 28 2021 3:09PM - Plan review process started sysadmin - Jul 14 2021 12:28PM - Plan Review letter sent to applicant sysadmin - Aug 2 2021 5:46AM - Permit approved subject to field inspections. | |||
Legacy Permitting Review | Approved w/ Conditions | 08/10/2021 | |
SysAdmin
|
|||
VP legacy plan review: Routt Environmental Health sysadmin - Jul 16 2021 1:55PM - Applicant has been emailed requirements. Submit directly to Routt County Environmental Health for review. sysadmin - Jul 19 2021 9:35AM - Retail Food and Child Care plan reviews required. sysadmin - Aug 10 2021 4:54PM - Reviews for child care and retail food approved. A pre-operational inspection by Environmental Health will be required after construction is complete and the facilities are ready for operations for Certificate of Occupancy signoff. | |||
Legacy Permitting Review | Approved | 07/21/2021 | |
SysAdmin
|
|||
VP legacy plan review: Mt Werner Water District sysadmin - Jul 6 2021 1:57PM - Sarah with Gensler working on PIF Qty take-off. sysadmin - Jul 14 2021 4:41PM - Hi Jon and Jim, Attached are the PIF Water and Sewer fees associated with the KVC move and tenant finish in the Sheraton, based on the proposed plans and fixture count take-off by Sarah. I’ve also attached the final signed agreement between the Sheraton and Mt Werner Water related to future fees in the area of interest. If you have any questions related to this agreement we would be happy to discuss, otherwise please stop by our offices with a check for the amount indicated and I will get the permit signed off. Regards, R sysadmin - Jul 21 2021 5:04PM - PIF fees paid 7-21-21 | |||
Fire Code Review | Approved w/ Conditions | 07/10/2021 | |
SysAdmin
|
|||
VP legacy plan review: Steamboat Fire Dept sysadmin - Jul 10 2021 11:20AM - Conditionally Approved –NO INSPECTIONS deferred submittal until RECEIPT of Fire Alarm/Sprinkler plan/permits by sub-contractor to Fire Prevention. See www.steamboatsprings.net, Fire and EMS Services, Fire Prevention, Downloadable Permits and Forms sysadmin - Jul 10 2021 11:20AM - Conditionally approved –NO INSPECTIONS pending submittal of Hood suppression system plan/permits by sub-contractor to Fire Prevention. See www.steamboatsprings.net | |||
Legacy Permitting Review | Approved | 07/01/2021 | |
SysAdmin
|
|||
VP legacy plan review: Routt Electrical Plan Review | |||
GIS Land Development Review | Approved | 06/30/2021 | |
SysAdmin
|
|||
VP legacy plan review: Steamboat Address | |||
Interim Construction Site Management | Approved | 06/30/2021 | |
SysAdmin
|
|||
VP legacy plan review: Steamboat Construction Site Management | |||
Planning Review | Approved | 06/28/2021 | |
SysAdmin
|
|||
VP legacy plan review: Steamboat Planning sysadmin - Jun 28 2021 4:24PM - OK - hotel use not changing. | |||
Finance Department Review | Approved | 06/28/2021 | |
SysAdmin
|
|||
VP legacy plan review: Steamboat Finance Dept sysadmin - Jun 28 2021 3:26PM - City taxes and fees $105,133.12 |
Inspection | Outcome | Requested | Scheduled | Date Inspected |
---|---|---|---|---|
Framing Inspection | Partial Pass | 9/13/2021 | 9/13/2021 | 09/13/2021 |
Don Marchbanks | ||||
Framing Inspection | Partial Pass | 09/20/2021 | ||
Todd Carr | ||||
Framing Inspection | Partial Pass | 10/7/2021 | 10/7/2021 | 10/07/2021 |
Don Marchbanks | ||||
Framing Inspection | Passed w/ Conditions | 10/20/2021 | 10/20/2021 | 10/20/2021 |
Todd Carr | ||||
Drywall Inspection | Partial Pass | 10/26/2021 | 10/26/2021 | 10/26/2021 |
Don Marchbanks | ||||
Drywall Inspection | Partial Pass | 11/15/2021 | 11/15/2021 | 11/15/2021 |
Todd Carr | ||||
Framing Inspection | Passed | 12/7/2021 | 12/7/2021 | 12/07/2021 |
Todd Carr | ||||
Building Final Inspection | Not Ready | 12/14/2021 | 12/14/2021 | 12/14/2021 |
Todd Carr | ||||
Building Final Inspection | Failed | 12/20/2021 | 12/20/2021 | 12/20/2021 |
Todd Carr | ||||
Corrections:
Miscellaneous
Carried Forward
12/20/2021
Contractor to complete the below work prior to full CO Approval:
1. B-21-745 complete all remaining work under this permit, door hardware installed and working properly including ADA power openers, permanent room signage throughout, complete sealing up all trade penetrations that go through fire assemblies, complete all kitchen work.
2. Complete and pass final electrical, plumbing and mechanical inspections parented to this building permit.
|
||||
Building Final Inspection | Partial Pass | 9/23/2022 | 9/23/2022 | 09/23/2022 |
Todd Carr | ||||
Corrections:
Building Department Corrections to be Completed
Carried Forward
09/23/2022
TCO approved
1. Door 161 needs a floor or hinge stop to stop the door just past 90 degrees, due to the door rubbing and staying open when it is fully opened.
2. K167 restroom has a mechanical exhaust fan with a switch on the ceiling, need to know if this suppose to run all the time, or why it's switched.
3. Add signage to changing rooms, note these are full of storage in two of the rooms so not sure if the room use needs to be changed, if so submit an addendum by Architect. Excess storage prevents access as well into these rooms, they must be cleaned up so the door will open a full 90 degrees, and access is allowed.
|
||||
Building Final Inspection | Passed | 10/10/2022 | 10/10/2022 | 10/10/2022 |
Todd Carr | ||||
Corrections:
Miscellaneous
Resolved
10/10/2022
Contractor to complete the below work prior to full CO Approval:
1. B-21-745 complete all remaining work under this permit, door hardware installed and working properly including ADA power openers, permanent room signage throughout, complete sealing up all trade penetrations that go through fire assemblies, complete all kitchen work.
2. Complete and pass final electrical, plumbing and mechanical inspections parented to this building permit.
|
||||
Building Final Inspection | Passed | 10/10/2022 | 10/10/2022 | 10/10/2022 |
Todd Carr | ||||
Corrections:
Building Department Corrections to be Completed
Resolved
10/10/2022
TCO approved
1. Door 161 needs a floor or hinge stop to stop the door just past 90 degrees, due to the door rubbing and staying open when it is fully opened.
2. K167 restroom has a mechanical exhaust fan with a switch on the ceiling, need to know if this suppose to run all the time, or why it's switched.
3. Add signage to changing rooms, note these are full of storage in two of the rooms so not sure if the room use needs to be changed, if so submit an addendum by Architect. Excess storage prevents access as well into these rooms, they must be cleaned up so the door will open a full 90 degrees, and access is allowed.
|
Condition | Status | Category |
---|---|---|
Miscellaneous Conditions | Resolved | Prior to Issuance of CO/CC |
Building Department
TCO approved
1. Door 161 needs a floor or hinge stop to stop the door just past 90 degrees, due to the door rubbing and staying open when it is fully opened.
2. K167 restroom has a mechanical exhaust fan with a switch on the ceiling, need to know if this suppose to run all the time, or why it's switched.
3. Add signage to changing rooms, note these are full of storage in two of the rooms so not sure if the room use needs to be changed, if so submit an addendum by Architect. Excess storage prevents access as well into these rooms, they must be cleaned up so the door will open a full 90 degrees, and access is allowed.
|
||
Miscellaneous Conditions | Resolved | Prior to Issuance of CO/CC |
Finance
Consent agreement executed due July 31, 2023
|
||
Miscellaneous Conditions | Resolved | Prior to Issuance of CO/CC |
Fire Prevention
The Fire Dept. is ok with a TCO at KVC. The following 3 items must be accomplished prior to CO.
1. New pull stations in KVC are currently sending alarm signal to panel and monitoring. New pull stations are not triggering notification devices in building and needs that fixed.
2. Add general alarm Horn/Strobe outside southwest entrance to KVC that now has remote annunciator.
3. Reprogram Horn/Strobe over Fire Dept. Connection at southwest corner of building to activate on fire sprinkler flow only.
|
Reference Number | Status | Type |
---|---|---|
SPREL210225 | Closed | Electrical |
SPRMH210707 | Canceled | Mechanical |
SPRMH210719 | Closed | Mechanical |