Permit Application Status
B-21-745
| Review Type | Outcome | Est. Completion Date | Completed |
|---|---|---|---|
| Fire Code Review | Approved | 01/13/2022 | |
| Building Code Review | TCO Approved | 12/24/2021 | 12/21/2021 |
| Building Code Review | TCO Approved | 12/21/2021 | |
| Planning Review | TCO Approved | 12/24/2021 | 12/21/2021 |
| Fire Code Review | TCO Approved | 12/24/2021 | 12/21/2021 |
| Finance Department Review | TCO Approved | 12/24/2021 | 12/20/2021 |
| External Agencies Review | TCO Approved | 12/20/2021 | |
| GIS Land Development Review | Approved | 12/24/2021 | 12/17/2021 |
| Legacy Permitting Review | Approved w/ Conditions | 08/11/2021 | |
| Legacy Permitting Review | Approved w/ Conditions | 08/10/2021 | |
| Legacy Permitting Review | Approved | 07/21/2021 | |
| Fire Code Review | Approved w/ Conditions | 07/10/2021 | |
| Legacy Permitting Review | Approved | 07/01/2021 | |
| GIS Land Development Review | Approved | 06/30/2021 | |
| Interim Construction Site Management | Approved | 06/30/2021 | |
| Planning Review | Approved | 06/28/2021 | |
| Finance Department Review | Approved | 06/28/2021 |
| Inspection | Outcome | Requested | Scheduled | Date Inspected |
|---|---|---|---|---|
| Framing Inspection | Partial Pass | 9/13/2021 | 9/13/2021 | 09/13/2021 |
| Don Marchbanks | ||||
| Framing Inspection | Partial Pass | 09/20/2021 | ||
| Todd Carr | ||||
| Framing Inspection | Partial Pass | 10/7/2021 | 10/7/2021 | 10/07/2021 |
| Don Marchbanks | ||||
| Framing Inspection | Passed w/ Conditions | 10/20/2021 | 10/20/2021 | 10/20/2021 |
| Todd Carr | ||||
| Drywall Inspection | Partial Pass | 10/26/2021 | 10/26/2021 | 10/26/2021 |
| Don Marchbanks | ||||
| Drywall Inspection | Partial Pass | 11/15/2021 | 11/15/2021 | 11/15/2021 |
| Todd Carr | ||||
| Framing Inspection | Passed | 12/7/2021 | 12/7/2021 | 12/07/2021 |
| Todd Carr | ||||
| Building Final Inspection | Not Ready | 12/14/2021 | 12/14/2021 | 12/14/2021 |
| Todd Carr | ||||
| Building Final Inspection | Failed | 12/20/2021 | 12/20/2021 | 12/20/2021 |
| Todd Carr | ||||
|
Corrections:
Miscellaneous
Carried Forward
12/20/2021
Contractor to complete the below work prior to full CO Approval:
1. B-21-745 complete all remaining work under this permit, door hardware installed and working properly including ADA power openers, permanent room signage throughout, complete sealing up all trade penetrations that go through fire assemblies, complete all kitchen work.
2. Complete and pass final electrical, plumbing and mechanical inspections parented to this building permit.
|
||||
| Building Final Inspection | Partial Pass | 9/23/2022 | 9/23/2022 | 09/23/2022 |
| Todd Carr | ||||
|
Corrections:
Building Department Corrections to be Completed
Carried Forward
09/23/2022
TCO approved
1. Door 161 needs a floor or hinge stop to stop the door just past 90 degrees, due to the door rubbing and staying open when it is fully opened.
2. K167 restroom has a mechanical exhaust fan with a switch on the ceiling, need to know if this suppose to run all the time, or why it's switched.
3. Add signage to changing rooms, note these are full of storage in two of the rooms so not sure if the room use needs to be changed, if so submit an addendum by Architect. Excess storage prevents access as well into these rooms, they must be cleaned up so the door will open a full 90 degrees, and access is allowed.
|
||||
| Building Final Inspection | Passed | 10/10/2022 | 10/10/2022 | 10/10/2022 |
| Todd Carr | ||||
|
Corrections:
Miscellaneous
Resolved
10/10/2022
Contractor to complete the below work prior to full CO Approval:
1. B-21-745 complete all remaining work under this permit, door hardware installed and working properly including ADA power openers, permanent room signage throughout, complete sealing up all trade penetrations that go through fire assemblies, complete all kitchen work.
2. Complete and pass final electrical, plumbing and mechanical inspections parented to this building permit.
|
||||
| Building Final Inspection | Passed | 10/10/2022 | 10/10/2022 | 10/10/2022 |
| Todd Carr | ||||
|
Corrections:
Building Department Corrections to be Completed
Resolved
10/10/2022
TCO approved
1. Door 161 needs a floor or hinge stop to stop the door just past 90 degrees, due to the door rubbing and staying open when it is fully opened.
2. K167 restroom has a mechanical exhaust fan with a switch on the ceiling, need to know if this suppose to run all the time, or why it's switched.
3. Add signage to changing rooms, note these are full of storage in two of the rooms so not sure if the room use needs to be changed, if so submit an addendum by Architect. Excess storage prevents access as well into these rooms, they must be cleaned up so the door will open a full 90 degrees, and access is allowed.
|
||||
| Condition | Status | Category |
|---|---|---|
| Miscellaneous Conditions | Resolved | Prior to Issuance of CO/CC |
|
Building Department
TCO approved
1. Door 161 needs a floor or hinge stop to stop the door just past 90 degrees, due to the door rubbing and staying open when it is fully opened.
2. K167 restroom has a mechanical exhaust fan with a switch on the ceiling, need to know if this suppose to run all the time, or why it's switched.
3. Add signage to changing rooms, note these are full of storage in two of the rooms so not sure if the room use needs to be changed, if so submit an addendum by Architect. Excess storage prevents access as well into these rooms, they must be cleaned up so the door will open a full 90 degrees, and access is allowed.
|
||
| Miscellaneous Conditions | Resolved | Prior to Issuance of CO/CC |
|
Finance
Consent agreement executed due July 31, 2023
|
||
| Miscellaneous Conditions | Resolved | Prior to Issuance of CO/CC |
|
Fire Prevention
The Fire Dept. is ok with a TCO at KVC. The following 3 items must be accomplished prior to CO.
1. New pull stations in KVC are currently sending alarm signal to panel and monitoring. New pull stations are not triggering notification devices in building and needs that fixed.
2. Add general alarm Horn/Strobe outside southwest entrance to KVC that now has remote annunciator.
3. Reprogram Horn/Strobe over Fire Dept. Connection at southwest corner of building to activate on fire sprinkler flow only.
|
||
| Reference Number | Status | Type |
|---|---|---|
| SPREL210225 | Closed | Electrical |
| SPRMH210707 | Canceled | Mechanical |
| SPRMH210719 | Closed | Mechanical |