B-21-745


In order to view fees, you need to be signed in. You will only be able to schedule inspections if you are a contact on the permit application.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

B-21-745
Alteration
Closed
GONDOLA SQUARE CONDOS
Alteration
E - Educational
I-4 - Institutional, day care facilities
INTERIOR RENOVATION OF A PORTION OF THE FIRST FLOOR OF THE EXISTING SHERATON HOTEL. WORK TO INCLUDE CONSTRUCTION OF NEW PARTITIONS, CEILINGS, CASEWORK, FINISHES, MECHANICAL, ELECTRICAL, PLUMBING & FIRE PROTECTION AS INDICATED ON DRAWINGS. KVC Kids vacation club.
06/22/2021
08/11/2021
08/11/2024
10/10/2022

Locations

Property
211077001

Address
2305 MT WERNER CIR

Permits

Permit Number: B-21-745

Building
Finaled

Permit Number: B-CU1

Change of Occupancy
Finaled

Reviews

Review Type Outcome Est. Completion Date Completed
Fire Code Review Approved 01/13/2022
Building Code Review TCO Approved 12/24/2021 12/21/2021
Building Code Review TCO Approved 12/21/2021
Planning Review TCO Approved 12/24/2021 12/21/2021
Fire Code Review TCO Approved 12/24/2021 12/21/2021
Finance Department Review TCO Approved 12/24/2021 12/20/2021
External Agencies Review TCO Approved 12/20/2021
GIS Land Development Review Approved 12/24/2021 12/17/2021
Legacy Permitting Review Approved w/ Conditions 08/11/2021
Legacy Permitting Review Approved w/ Conditions 08/10/2021
Legacy Permitting Review Approved 07/21/2021
Fire Code Review Approved w/ Conditions 07/10/2021
Legacy Permitting Review Approved 07/01/2021
GIS Land Development Review Approved 06/30/2021
Interim Construction Site Management Approved 06/30/2021
Planning Review Approved 06/28/2021
Finance Department Review Approved 06/28/2021

Inspections

Inspection Outcome Requested Scheduled Date Inspected
Framing Inspection Partial Pass 9/13/2021 9/13/2021 09/13/2021
Don Marchbanks
Framing Inspection Partial Pass 09/20/2021
Todd Carr
Framing Inspection Partial Pass 10/7/2021 10/7/2021 10/07/2021
Don Marchbanks
Framing Inspection Passed w/ Conditions 10/20/2021 10/20/2021 10/20/2021
Todd Carr
Drywall Inspection Partial Pass 10/26/2021 10/26/2021 10/26/2021
Don Marchbanks
Drywall Inspection Partial Pass 11/15/2021 11/15/2021 11/15/2021
Todd Carr
Framing Inspection Passed 12/7/2021 12/7/2021 12/07/2021
Todd Carr
Building Final Inspection Not Ready 12/14/2021 12/14/2021 12/14/2021
Todd Carr
Building Final Inspection Failed 12/20/2021 12/20/2021 12/20/2021
Todd Carr
Corrections:


Miscellaneous
Carried Forward
12/20/2021
Contractor to complete the below work prior to full CO Approval: 1. B-21-745 complete all remaining work under this permit, door hardware installed and working properly including ADA power openers, permanent room signage throughout, complete sealing up all trade penetrations that go through fire assemblies, complete all kitchen work. 2. Complete and pass final electrical, plumbing and mechanical inspections parented to this building permit.

Building Final Inspection Partial Pass 9/23/2022 9/23/2022 09/23/2022
Todd Carr
Corrections:


Building Department Corrections to be Completed
Carried Forward
09/23/2022
TCO approved 1. Door 161 needs a floor or hinge stop to stop the door just past 90 degrees, due to the door rubbing and staying open when it is fully opened. 2. K167 restroom has a mechanical exhaust fan with a switch on the ceiling, need to know if this suppose to run all the time, or why it's switched. 3. Add signage to changing rooms, note these are full of storage in two of the rooms so not sure if the room use needs to be changed, if so submit an addendum by Architect. Excess storage prevents access as well into these rooms, they must be cleaned up so the door will open a full 90 degrees, and access is allowed.

Building Final Inspection Passed 10/10/2022 10/10/2022 10/10/2022
Todd Carr
Corrections:


Miscellaneous
Resolved
10/10/2022
Contractor to complete the below work prior to full CO Approval: 1. B-21-745 complete all remaining work under this permit, door hardware installed and working properly including ADA power openers, permanent room signage throughout, complete sealing up all trade penetrations that go through fire assemblies, complete all kitchen work. 2. Complete and pass final electrical, plumbing and mechanical inspections parented to this building permit.

Building Final Inspection Passed 10/10/2022 10/10/2022 10/10/2022
Todd Carr
Corrections:


Building Department Corrections to be Completed
Resolved
10/10/2022
TCO approved 1. Door 161 needs a floor or hinge stop to stop the door just past 90 degrees, due to the door rubbing and staying open when it is fully opened. 2. K167 restroom has a mechanical exhaust fan with a switch on the ceiling, need to know if this suppose to run all the time, or why it's switched. 3. Add signage to changing rooms, note these are full of storage in two of the rooms so not sure if the room use needs to be changed, if so submit an addendum by Architect. Excess storage prevents access as well into these rooms, they must be cleaned up so the door will open a full 90 degrees, and access is allowed.

Conditions

Condition Status Category
Miscellaneous Conditions Resolved Prior to Issuance of CO/CC
Building Department
TCO approved 1. Door 161 needs a floor or hinge stop to stop the door just past 90 degrees, due to the door rubbing and staying open when it is fully opened. 2. K167 restroom has a mechanical exhaust fan with a switch on the ceiling, need to know if this suppose to run all the time, or why it's switched. 3. Add signage to changing rooms, note these are full of storage in two of the rooms so not sure if the room use needs to be changed, if so submit an addendum by Architect. Excess storage prevents access as well into these rooms, they must be cleaned up so the door will open a full 90 degrees, and access is allowed.
Miscellaneous Conditions Resolved Prior to Issuance of CO/CC
Finance
Consent agreement executed due July 31, 2023
Miscellaneous Conditions Resolved Prior to Issuance of CO/CC
Fire Prevention
The Fire Dept. is ok with a TCO at KVC. The following 3 items must be accomplished prior to CO. 1. New pull stations in KVC are currently sending alarm signal to panel and monitoring. New pull stations are not triggering notification devices in building and needs that fixed. 2. Add general alarm Horn/Strobe outside southwest entrance to KVC that now has remote annunciator. 3. Reprogram Horn/Strobe over Fire Dept. Connection at southwest corner of building to activate on fire sprinkler flow only.

Related Permit & Planning Applications

Reference Number Status Type
SPREL210225 Closed Electrical
SPRMH210707 Canceled Mechanical
SPRMH210719 Closed Mechanical

Documents & Images

Date Uploaded File Type Name
CERTIFICATE OF OCCUPANCY.PDF
CERTIFICATE OF TEMPORARY OCCUPANCY.PDF
CERTIFICATE OF TEMPORARY OCCUPANCY.PDF
INSPECTION REPORT.PDF
INSPECTION REPORT.PDF
INSPECTION REPORT.PDF
INSPECTION REPORT.PDF
INSPECTION REPORT.PDF
INSPECTION REPORT.PDF
INSPECTION REPORT.PDF
INSPECTION REPORT.PDF
INSPECTION REPORT.PDF
INSPECTION REPORT.PDF