Permit Application Status
SPRRN241466
In order to view fees, you need to be signed in. You will only be able to schedule inspections if you are a contact on the permit application.
        Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.
| Date Returned | Name | 
|---|---|
| 10/31/2024 | ArchitecturalDrawings_RiverfrontParkUnit2_Permit_24018 (Stamped) | 
| 01/15/2025 | Site Plan SIDEWALK EASEMENT Recorded 122324 (Stamped) | 
| 10/31/2024 | Structural Drawings (Stamped) | 
| 10/31/2024 | Mechanical-PlumbingDrawings_Riverfront Park_Revised Permit (Stamped) | 
| 03/14/2025 | Ventilation Report 02.27.2025 (Stamped) | 
| Review Type | Outcome | Est. Completion Date | Completed | 
|---|---|---|---|
| COO Review - Planning | TCO Approved | 11/03/2025 | 10/27/2025 | 
| 
                                                             
                                    Jeremy Brown
                                    
                                 
                             | 
                        |||
| COO Review - Building Code | Approved | 07/30/2025 | 07/23/2025 | 
| 
                                                             
                                    Todd Carr
                                    
                                 
                             | 
                        |||
| COO Review - Finance Department | Approved | 07/29/2025 | 07/22/2025 | 
| 
                                                             
                                    Denitsa Yaneva
                                    
                                 
                             | 
                        |||
| COO Review - Building Code | Failed | 05/23/2025 | 05/23/2025 | 
| 
                                                             
                                    Malea Michael-Ferrier
                                    
                                 
                             | 
                        |||
| Failed. Must pass final electrical inspection for TCO. Must complete Condition #5 for CO. | |||
| COO Review - Planning | Failed | 04/02/2025 | 04/22/2025 | 
| 
                                                             
                                    Jeremy Brown
                                    
                                 
                             | 
                        |||
| TCO/CO Review | |||
| COO Review - Fire Code | Approved | 04/02/2025 | 04/03/2025 | 
| 
                                                             
                                    Shannon Yaconiello
                                    
                                 
                             | 
                        |||
| CC Approved. [Shannon Yaconiello @ 04/03/2025 11:38 AM] | |||
| COO Review - GIS Land Development | Approved | 04/02/2025 | 04/03/2025 | 
| 
                                                             
                                    Colten Yoast
                                    
                                 
                             | 
                        |||
| New addresses are added. | |||
| COO Review - Building Code | Failed | 04/02/2025 | 04/02/2025 | 
| 
                                                             
                                    Todd Carr
                                    
                                 
                             | 
                        |||
| TCO/CO Review and check to see if Electrical permit has been applied for, issued, and inspected, we did get mechanical and plumbing permits but I see no electrical permit. We need the ventilationa and bath exhaust fan checked by mechanical engineer as well, see two open condtions. Plus building final did not pass. | |||
| Building Code Review | Approved | 03/14/2025 | |
| 
                                                             
                                    Todd Carr
                                    
                                 
                             | 
                        |||
| Main Floor Ventilation plan approved. | |||
| GIS Land Development Review | Approved | 10/30/2024 | 10/31/2024 | 
| 
                                                             
                                    Malea Michael-Ferrier
                                    
                                 
                             | 
                        |||
| 
                                         
                                            Miscellaneous
                                         
                                        Resolved 
11/04/2024 
                                            Prior to TCO being approved, the City of Steamboat Springs GIS Department will need to assign final Building Addressing and Unit Numbers and Letters to all of 1900 and 1920 Bridge Lane. 
                                         
                                        
                                        
                                     | 
                                |||
| We need a secondary address assigned to this permit for the secondary residence. Please contact me at cyoast@steamboatsprings.net | |||
| Building Code Review | Approved | 10/30/2024 | 10/25/2024 | 
| 
                                                             
                                    Todd Carr
                                    
                                 
                             | 
                        |||
| 
                                         
                                            Building Department Corrections to be Completed
                                         
                                        Resolved 
10/25/2024 
                                            The Value of Work to be Permitted and the Total Construction Valuation are too low of values for us to accept for the amount of new construction that has taken place since the last time this unit was previously approved under issued building permits. On all of these units located at 1900-1920 Bridge Lane, the Building Department has set a cost factor for all new residential dwellings created at 1900-1920 Bridge lane, the Square Footage Cost of $100.00 per square foot for Total Construction Valuation, and $75.00 per square foot for Value of Work to be Permitted to calculate all tax fees due and permit fees due on these projects to be consistent, fair and equal to all owners of these units. For all units that have alteration work done in other areas of the Building on commercial space such as storage rooms, offices, garage space, we will use $40 per square foot for Total Project Valuation, and use $30 for Value of Work to be Permitted.
All new work that has to be performed as a result of our permitting process in terms of new products, materials, appliances, equipment, and labor to install, will be added to the above square footage cost of work done previously without permits in the past, we have added a Condition to this permit that we will not provide a Certificate of Occupancy until the owner has turned in all contracts associated with hiring professional to do the work, and invoices or receipts showing all costs of materials and products purchased. If an owner is doing their own work, then labor is calculated by taking all invoices and receipts for materials and products purchased and multiplied by two to calculate labor. The owner will then be responsible to pay these fees that are accessed to the permit at the end of the project after the contractors for services, receipts, and invoices are reviewed by the Building Department prior to Certificate of Occupancy being issued.
                                         
                                        
                                        
                                     | 
                                |||
| 
                                         
                                            Building Department Corrections to be Completed
                                         
                                        Resolved 
10/25/2024 
                                            On Sheet A-2 and A-3 these are acting as fire Separation Plans and Use Plans, but not a full floor plan that would provide us actual room dimensions, door sizes, ADA clearance circle in the bathroom on A-2, and hallway dimensions as well. You may either update Sheet A-2 and A-3 to add these details and dimenisions or you may produce to actual floor plans, your choice.
                                         
                                        
                                        
                                     | 
                                |||
| 
                                         
                                            Building Department Corrections to be Completed
                                         
                                        Resolved 
10/25/2024 
                                            Please show us the location of the mechanical room for the new R-2 unit on the 2nd floor, we also need to know what type of heating equipment is installed in this unit to heat the new apartment, and also what type of water heater is installed to provide hot water to this unit. Please verify or tell us the bathroom in the new apartment has a bath exhaust fan, or does it meet an exception with the correct sized operable window per the exception. Also we need to know how ventilation requirements are being met in the new apartment per the sections below from the IEBC Alteration Level 2.
807.1 Reconfigured or converted spaces.
Reconfigured spaces intended for occupancy and spaces converted to habitable or occupiable space in any work area shall be provided with natural or mechanical ventilation in accordance with the International Mechanical Code.
Exception: Existing mechanical ventilation systems shall comply with the requirements of Section 807.2.
807.2 Altered existing systems.
In mechanically ventilated spaces, existing mechanical ventilation systems that are altered, reconfigured or extended shall provide not less than 5 cubic feet per minute (cfm) (0.0024 m3/s) per person of outdoor air and not less than 15 cfm (0.0071 m3/s) of ventilation air per person, or not less than the amount of ventilation air determined by the Indoor Air Quality Procedure of ASHRAE 62.1.
                                         
                                        
                                        
                                     | 
                                |||
| 
                                         
                                            Building Department Corrections to be Completed
                                         
                                        Resolved 
10/25/2024 
                                            On the main floor we assume this is in-floo heat system that heats the entire space. how is ventilation requirements being met for the new offices per the 2021 IMC, see IEBC Sections below from Alteration Level 2.
807.1 Reconfigured or converted spaces.
Reconfigured spaces intended for occupancy and spaces converted to habitable or occupiable space in any work area shall be provided with natural or mechanical ventilation in accordance with the International Mechanical Code.
Exception: Existing mechanical ventilation systems shall comply with the requirements of Section 807.2.
807.2 Altered existing systems.
In mechanically ventilated spaces, existing mechanical ventilation systems that are altered, reconfigured or extended shall provide not less than 5 cubic feet per minute (cfm) (0.0024 m3/s) per person of outdoor air and not less than 15 cfm (0.0071 m3/s) of ventilation air per person, or not less than the amount of ventilation air determined by the Indoor Air Quality Procedure of ASHRAE 62.1.
                                         
                                        
                                        
                                     | 
                                |||
| 
                                         
                                            Building Department Corrections to be Completed
                                         
                                        Resolved 
10/25/2024 
                                            Are than any penetrations of any MEP's through any fire assemblies that are not completely enclosed within cavities that we will be dealing with on this project?
                                         
                                        
                                        
                                     | 
                                |||
| Permit approved. | |||
| Utilities Review - City | Approved | 10/02/2024 | 10/03/2024 | 
| 
                                                             
                                    Amber Gregory
                                    
                                 
                             | 
                        |||
| GIS Land Development Review | Failed | 10/02/2024 | 10/02/2024 | 
| 
                                                             
                                    Colten Yoast
                                    
                                 
                             | 
                        |||
| No sub unit plan discussed. Please contact me at 970-871-8229 or at cyoast@steamboatsprings.net | |||
| Planning Review | Approved | 10/02/2024 | 10/02/2024 | 
| 
                                                             
                                    Jeremy Brown
                                    
                                 
                             | 
                        |||
| Engineering Review | Approved | 10/02/2024 | 10/02/2024 | 
| 
                                                             
                                    Emrick Soltis, P.E., CFM
                                    
                                 
                             | 
                        |||
| Finance Department Review | Approved | 10/02/2024 | 09/30/2024 | 
| 
                                                             
                                    Sondra Spratta
                                    
                                 
                             | 
                        |||
| Building Code Review | Failed | 10/02/2024 | 09/30/2024 | 
| 
                                                             
                                    Todd Carr
                                    
                                 
                             | 
                        |||
| 
                                         
                                            Building Department Corrections to be Completed
                                         
                                        Carried Forward 
10/23/2024 
                                            The Value of Work to be Permitted and the Total Construction Valuation are too low of values for us to accept for the amount of new construction that has taken place since the last time this unit was previously approved under issued building permits. On all of these units located at 1900-1920 Bridge Lane, the Building Department has set a cost factor for all new residential dwellings created at 1900-1920 Bridge lane, the Square Footage Cost of $100.00 per square foot for Total Construction Valuation, and $75.00 per square foot for Value of Work to be Permitted to calculate all tax fees due and permit fees due on these projects to be consistent, fair and equal to all owners of these units. For all units that have alteration work done in other areas of the Building on commercial space such as storage rooms, offices, garage space, we will use $40 per square foot for Total Project Valuation, and use $30 for Value of Work to be Permitted.
All new work that has to be performed as a result of our permitting process in terms of new products, materials, appliances, equipment, and labor to install, will be added to the above square footage cost of work done previously without permits in the past, we have added a Condition to this permit that we will not provide a Certificate of Occupancy until the owner has turned in all contracts associated with hiring professional to do the work, and invoices or receipts showing all costs of materials and products purchased. If an owner is doing their own work, then labor is calculated by taking all invoices and receipts for materials and products purchased and multiplied by two to calculate labor. The owner will then be responsible to pay these fees that are accessed to the permit at the end of the project after the contractors for services, receipts, and invoices are reviewed by the Building Department prior to Certificate of Occupancy being issued. 
                                         
                                        
                                        
                                     | 
                                |||
| 
                                         
                                            Building Department Corrections to be Completed
                                         
                                        Carried Forward 
10/23/2024 
                                            On Sheet A-2 and A-3 these are acting as fire Separation Plans and Use Plans, but not a full floor plan that would provide us actual room dimensions, door sizes, ADA clearance circle in the bathroom on A-2, and hallway dimensions as well. You may either update Sheet A-2 and A-3 to add these details and dimenisions or you may produce to actual floor plans, your choice. 
                                         
                                        
                                        
                                     | 
                                |||
| 
                                         
                                            Building Department Corrections to be Completed
                                         
                                        Carried Forward 
10/23/2024 
                                            Please show us the location of the mechanical room for the new R-2 unit on the 2nd floor, we also need to know what type of heating equipment is installed in this unit to heat the new apartment, and also what type of water heater is installed to provide hot water to this unit. Please verify or tell us the bathroom in the new apartment has a bath exhaust fan, or does it meet an exception with the correct sized operable window per the exception. Also we need to know how ventilation requirements are being met in the new apartment per the sections below from the IEBC Alteration Level 2.
807.1 Reconfigured or converted spaces.
Reconfigured spaces intended for occupancy and spaces converted to habitable or occupiable space in any work area shall be provided with natural or mechanical ventilation in accordance with the International Mechanical Code.
Exception: Existing mechanical ventilation systems shall comply with the requirements of Section 807.2.
807.2 Altered existing systems.
In mechanically ventilated spaces, existing mechanical ventilation systems that are altered, reconfigured or extended shall provide not less than 5 cubic feet per minute (cfm) (0.0024 m3/s) per person of outdoor air and not less than 15 cfm (0.0071 m3/s) of ventilation air per person, or not less than the amount of ventilation air determined by the Indoor Air Quality Procedure of ASHRAE 62.1.
                                         
                                        
                                        
                                     | 
                                |||
| 
                                         
                                            Building Department Corrections to be Completed
                                         
                                        Carried Forward 
10/23/2024 
                                            On the main floor we assume this is in-floo heat system that heats the entire space. how is ventilation requirements being met for the new offices per the 2021 IMC, see IEBC Sections below from Alteration Level 2.
807.1 Reconfigured or converted spaces.
Reconfigured spaces intended for occupancy and spaces converted to habitable or occupiable space in any work area shall be provided with natural or mechanical ventilation in accordance with the International Mechanical Code.
Exception: Existing mechanical ventilation systems shall comply with the requirements of Section 807.2.
807.2 Altered existing systems.
In mechanically ventilated spaces, existing mechanical ventilation systems that are altered, reconfigured or extended shall provide not less than 5 cubic feet per minute (cfm) (0.0024 m3/s) per person of outdoor air and not less than 15 cfm (0.0071 m3/s) of ventilation air per person, or not less than the amount of ventilation air determined by the Indoor Air Quality Procedure of ASHRAE 62.1.
                                         
                                        
                                        
                                     | 
                                |||
| 
                                         
                                            Building Department Corrections to be Completed
                                         
                                        Carried Forward 
10/23/2024 
                                             Are than any penetrations of any MEP's through any fire assemblies that are not completely enclosed within cavities that we will be dealing with on this project?
                                         
                                        
                                        
                                     | 
                                |||
| Please see below corrections and comments on the application. | |||
| Fire Code Review | Approved | 10/02/2024 | 09/29/2024 | 
| 
                                                             
                                    Nick Kuchulis
                                    
                                 
                             | 
                        |||
| Conditionally Approved –NO INSPECTIONS deferred submittal until RECEIPT of Fire Alarm/Sprinkler plan/permits by sub-contractor to Fire Prevention. See www.steamboatsprings.net/Fire and EMS Services/Fire Prevention/Downloadable Permits and Forms [Nick Kuchulis @ 09/29/2024 6:15 PM] | |||
| Inspection | Outcome | Requested | Scheduled | Date Inspected | 
|---|---|---|---|---|
| Framing Inspection | Partial Pass | 11/20/2024 | 11/20/2024 | |
| Todd Carr | ||||
| Footing Inspection | Partial Pass | 12/5/2024 | 12/05/2024 | |
| Jeff Yeiser | ||||
| Wall/Roof Sheeting | Not Ready | 12/27/2024 | 12/27/2024 | 12/27/2024 | 
| Silas Ebbert | ||||
| Framing Inspection | Partial Pass | 12/27/2024 | ||
| Silas Ebbert | ||||
| 
                                
                                     Corrections: 
                                    
                                    Building Department Corrections to be Completed
                                 
                                Carried Forward 
12/27/2024 
Install header and hangers at front entry and fasten ledgers better
Contact engineer about back stairway as built conditions and if second LVL ply is needed.  
 | 
                        ||||
| Footing Inspection | Not Ready | 12/27/2024 | 12/27/2024 | 12/27/2024 | 
| Silas Ebbert | ||||
| Framing Inspection | Partial Pass | 01/06/2025 | ||
| Silas Ebbert | ||||
| 
                                
                                     Corrections: 
                                    
                                    Building Department Corrections to be Completed
                                 
                                Resolved 
01/06/2025 
Install header and hangers at front entry and fasten ledgers better
Contact engineer about back stairway as built conditions and if second LVL ply is needed. 
 | 
                        ||||
| 
                                
                                 
                                    Building Department Corrections to be Completed
                                 
                                Carried Forward 
01/06/2025 
Building Department Corrections to be Completed
1. Add ledger fasteners  into studs on old mezzanine area floor 
 | 
                        ||||
| Footing Inspection | Passed | 1/6/2025 | 1/6/2025 | 01/06/2025 | 
| Silas Ebbert | ||||
| Framing Inspection | Not Ready | 1/22/2025 | 01/21/2025 | |
| Todd Carr | ||||
| 
                                
                                     Corrections: 
                                    
                                    Building Department Corrections to be Completed
                                 
                                Carried Forward 
01/21/2025 
Building Department Corrections to be Completed
1. Add ledger fasteners  into studs on old mezzanine area floor 
 | 
                        ||||
| Drywall Inspection | Partial Pass | 01/28/2025 | ||
| Silas Ebbert | ||||
| Insulation Inspection | Not Ready | 1/28/2025 | 1/28/2025 | 01/28/2025 | 
| Silas Ebbert | ||||
| Drywall Inspection | Partial Pass | 2/25/2025 | 02/25/2025 | |
| Silas Ebbert | ||||
| Drywall Inspection | Partial Pass | 3/7/2025 | 3/7/2025 | 03/07/2025 | 
| Silas Ebbert | ||||
| Drywall Inspection | Partial Pass | 3/10/2025 | 3/10/2025 | 03/10/2025 | 
| Silas Ebbert | ||||
| Drywall Inspection | Passed | 3/12/2025 | 3/14/2025 | 03/14/2025 | 
| Silas Ebbert | ||||
| Building Final Inspection | Failed | 3/26/2025 | 3/26/2025 | 03/26/2025 | 
| Silas Ebbert | ||||
| 
                                
                                     Corrections: 
                                    
                                    Building Department Corrections to be Completed
                                 
                                Carried Forward 
03/26/2025 
Building Department Corrections to be Completed
1. Install self closing hinges and smoke seals on fire door
2. Pass final electrical inspection 
 | 
                        ||||
| Building Final Inspection | Passed | 5/22/2025 | 5/22/2025 | 05/22/2025 | 
| Silas Ebbert | ||||
| 
                                
                                     Corrections: 
                                    
                                    Building Department Corrections to be Completed
                                 
                                Resolved 
05/22/2025 
Building Department Corrections to be Completed
1. Install self closing hinges and smoke seals on fire door
2. Pass final electrical inspection 
 | 
                        ||||
| Condition | Status | Category | 
|---|---|---|
| Miscellaneous Conditions | Resolved | Prior to Rough Building Wall Inspections | 
|                 
                 Fire Prevention 
Conditionally Approved –NO INSPECTIONS deferred submittal until RECEIPT of Fire Alarm/Sprinkler plan/permits by sub-contractor to Fire Prevention. See www.steamboatsprings.net/Fire and EMS Services/Fire Prevention/Downloadable Permits and Forms [Nick Kuchulis @ 09/29/2024 6:15 PM]  
 |            
        ||
| Final Fire Inspection Required | Resolved | Prior to Issuance of CO/CC | 
|                 
                 Fire Prevention 
Final Fire Alarm and Sprinkler Inspections Required.  [Shannon Yaconiello @ 09/30/2024 9:49 AM]  
 |            
        ||
| MF/Com/I Planning CO Review | Resolved | Prior to Issuance of TCO/CO/CC | 
|                 
                 Planning Department 
Prior to issuance of a Temporary Certificate of Occupancy (or Certificate of Occupancy), the Department of Planning and Community Development will inspect the site to ensure the project has been built in accordance with the approved plans and the Community Development Code.  Specifically this will include inspection of parking lot striping.  [Jeremy Brown @ 04/23/2025 7:55 AM]  
 |            
        ||
| Vested Approval Conditions | Resolved | Prior to Issuance of TCO/CO/CC | 
|                 
                 Planning Department 
Compliance with PL20240033 conditions of approval required. 
 |            
        ||
| Building Department Conditions to be Completed | Resolved | Prior to Issuance of CO/CC | 
|                 
                 Building Department 
Prior to Certificate of Occupancy being Issued, Owner/Applicant must pay all additional Fees due as a result of all new work completed that did not previously exist prior to permit issuance.
All new work that has to be performed as a result of our permitting process in terms of new products, materials, appliances, equipment, and labor to install, will be added to the above square footage cost of work done previously without permits in the past, we have added a Condition to this permit that we will not provide a Certificate of Occupancy until the owner has turned in all contracts associated with hiring professional to do the work, and invoices or receipts showing all costs of materials and products purchased. If an owner is doing their own work, then labor is calculated by taking all invoices and receipts for materials and products purchased and multiplied by two to calculate labor. The owner will then be responsible to pay these fees that are accessed to the permit at the end of the project after the contractors for services, receipts, and invoices are reviewed by the Building Department prior to Certificate of Occupancy being issued. 
Initial Costs were calculated off drawings: 
R-2 new apartment on level 2 has 1251 SQ FT x 100 = $125,100  and 1251 SQ FT x 75 = $93,825
New Office Space level 1 has 1429 SQ FT x 40 = $57,100 and 1429 SQ FT x 30 = $ 42,870
Total Project Valuation is $182,200
Total Value of Work Permitted is $136,695
 [Todd Carr @ 10/23/2024 1:17 PM] 
 
 |            
        ||
| Building Department Conditions to be Completed | Resolved | Prior to Issuance of CO/CC | 
|                 
                 Building Department 
All Building, Electrical, Mechanical, Plumbing, or Gas Permits will have an expiration date of 1-year set on these permits once they are issued, all work must be completed within one year due to the Life Safety issues created as a result of performing work without a permit.  [Todd Carr @ 10/04/2024 7:22 AM]  
 |            
        ||
| Building Department Conditions to be Completed | Resolved | Prior to Issuance of TCO/CO/CC | 
|                 
                 Building Department 
 [Todd Carr @ 10/04/2024 7:24 AM] Applicants/Owners must apply for an Electrical Permiit and complete all inspections prior to TCO. 
 |            
        ||
| Building Department Conditions to be Completed | Resolved | Prior to Full Building Permit Issuance | 
|                 
                 Building Department 
Prior to permit issuance, applicant/owner must schedule a pre-inspection walk-through with the Building Official, to review and determine the amount of work that must be done on the project to meet the approved plans, to review what is there in terms of exisitng construction that is approved in it's existing condition, and what work must be done that is not approved or does not meet the approved plans at the start of the project. [Todd Carr @ 10/04/2024 10:36 AM]   
 |            
        ||
| Miscellaneous Conditions | Resolved | Prior to Issuance of TCO/CO/CC | 
|                 
                 GIS 
Prior to TCO being approved, the City of Steamboat Springs GIS Department will need to assign final Building Addressing and Unit Numbers and Letters to all of 1900 and 1920 Bridge Lane. 
 
 |            
        ||
| Building Department Conditions to be Completed | Resolved | |
|                 
                 Building Department 
Building Department Conditions to be Completed
1. Bighorn Mechanical Engineers need to be consulted on the downs stairs bathroom fan that is called on plans to be continuously running. This fan exhausts into the hallway instead of terminating outside. This bathroom and overall project was built under the 2003 I codes and we need the mechanical engineers to assess whether with bathroom needs to be ventilated at all and if then the bathroom and hallway areas need ventilation requirements that could be met with removing doors between rooms with windows and the hallway or installing transfer grills.
From 2003 IBC
1203.4.2.1 Bathrooms.
Rooms containing bathtubs, showers, spas and similar bathing fixtures shall be mechanically ventilated in accordance with the International Mechanical Code.
 
 |            
        ||
| Miscellaneous Conditions | Open | Prior to Issuance of CO/CC | 
|                 
                 Planning Department 
Prior to issuance of a full Certificate of Occupancy, the Department of Planning and Community Development will inspect the site to ensure the project has been built in accordance with the approved plans and the Community Development Code.  Specifically this will include inspection of landscape plantings and interior parking lot landscape forms.  [Jeremy Brown @ 04/23/2025 7:55 AM] 
Site Inspection on 10/17 showed missing striping of two spaces along the Eastern property line, along with 2 missing ADA spaces.  Prior to full CO, these issues must be resolved.  [Jeremy Brown @ 10/27/2025 4:25 PM]  
 |            
        ||
| Use Tax Reconciliation | Resolved | Prior to Issuance of CO/CC | 
|                 
                 Finance 
Use Tax Recon work must be completed with City Finance: Contact the city directly for more information @ constructionusetax@steamboatsprings.net 
 |            
        ||
| Reference Number | Status | Type | 
|---|---|---|
| SPRPL241916 | Closed | Plumbing | 
| SPRMH250116 | Closed | Mechanical | 
| SPREL250417 | Closed | Electrical | 