Permit Application Status
SPRRN220704
In order to view fees, you need to be signed in. You will only be able to schedule inspections if you are a contact on the permit application.
Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.
Review Type | Outcome | Est. Completion Date | Completed |
---|---|---|---|
COO Review - Planning | Approved | 11/22/2022 | 11/21/2022 |
Bob Keenan, AICP
|
|||
COO Review - Building Code | TCO Approved | 11/22/2022 | 11/18/2022 |
Heidi Spengler
|
|||
TCO approved | |||
COO Review - Finance Department | TCO Approved | 11/22/2022 | 11/16/2022 |
Amy Camilletti
|
|||
The City of Steamboat Springs Finance department has approved a TEMPORARY CERTIFICATE (TCO/TCC) on this project. A construction use tax reconciliation is required within 90 days to be compliant with the City of Steamboat Springs Municipal Code AND before signoff for the FINAL certificate of occupancy/completion with the Routt County Building Department. This information is sent to the email listed in City View. Please forward this information to the appropriate person to get this completed timely. | |||
COO Review - Fire Code | Approved | 11/22/2022 | 11/15/2022 |
Shannon Yaconiello
|
|||
CC Approved - SY | |||
Electrical Review | Approved | 09/22/2022 | 09/19/2022 |
Tom Cook
|
|||
Addendum submitted 9.14.22 final approval subject to field inspection | |||
Utilities Review - Mt. Werner | Approved | 09/22/2022 | 09/16/2022 |
Richard Buccino
|
|||
Addendum submitted 9.14.22 | |||
Building Code Review | Approved | 09/22/2022 | 09/16/2022 |
Ted Allen
|
|||
Miscellaneous
Resolved
09/16/2022
Certain piping that is shown on Sheet 2B-P1.201 appears to be installed in conflict with IBC Section 1023.5 that regulates penetrations in interior exit stairways and where penetrations are allowed per exception: Membrane penetrations shall be permitted on the outside of the interior exit stairway and ramp. Such penetrations shall be protected in accordance with Section 714.4.2. Please resubmit plans with tested penetration fire assemblies with rating to comply with IBC Section 1023.1 (fire-resistance rating of not less than 2 hours where connecting four stories or more and not less than 1 hour where connecting less than four stories).
|
|||
Miscellaneous
Resolved
09/16/2022
Addendum, documents uploaded on 07/19/2022 include adding new restroom with plumbing plans that require utility sign-off from Mt. Werner and also electrical plans for review and approval by RCRBD electrical inspector.
|
|||
Addendum submitted 9.14.22 | |||
Building Code Review | Failed | 07/26/2022 | 07/21/2022 |
Ted Allen
|
|||
Miscellaneous
Carried Forward
09/15/2022
Certain piping that is shown on Sheet 2B-P1.201 appears to be installed in conflict with IBC Section 1023.5 that regulates penetrations in interior exit stairways and where penetrations are allowed per exception: Membrane penetrations shall be permitted on the outside of the interior exit stairway and ramp. Such penetrations shall be protected in accordance with Section 714.4.2. Please resubmit plans with tested penetration fire assemblies with rating to comply with IBC Section 1023.1 (fire-resistance rating of not less than 2 hours where connecting four stories or more and not less than 1 hour where connecting less than four stories).
|
|||
Miscellaneous
Carried Forward
09/15/2022
Addendum, documents uploaded on 07/19/2022 include adding new restroom with plumbing plans that require utility sign-off from Mt. Werner and also electrical plans for review and approval by RCRBD electrical inspector.
|
|||
Addendum, documents uploaded on 07/19/2022 | |||
Planning Review | Approved | 06/16/2022 | 06/16/2022 |
Bob Keenan, AICP
|
|||
Construction Site Management Review | Approved | 06/16/2022 | 06/14/2022 |
Scott Slamal
|
|||
Electrical Review | Approved | 06/16/2022 | 06/09/2022 |
Tom Cook
|
|||
Final approval subject to field inspection | |||
Building Code Review | Approved | 06/16/2022 | 06/08/2022 |
Ted Allen
|
|||
Fire Code Review | Approved | 06/16/2022 | 06/07/2022 |
Charles Brookshire
|
|||
Conditionally Approved –NO INSPECTIONS deferred submittal until RECEIPT of Fire Alarm/Sprinkler plan/permits by sub-contractor to Fire Prevention. See www.steamboatsprings.net, Fire and EMS Services, Fire Prevention, Downloadable Permits and Forms. NB | |||
Finance Department Review | Approved | 06/16/2022 | 06/07/2022 |
Sondra Spratta
|
|||
City taxes and fees $7,250.00 | |||
Utilities Review - Mt. Werner | Approved | 06/16/2022 | 06/06/2022 |
Richard Buccino
|
|||
Inspection | Outcome | Requested | Scheduled | Date Inspected |
---|---|---|---|---|
Structural Inspection | Partial Pass | 9/27/2022 | 9/27/2022 | 09/27/2022 |
Ron Norton | ||||
Drywall Inspection | Partial Pass | 9/29/2022 | 9/29/2022 | 09/29/2022 |
Ron Norton | ||||
Insulation Inspection | Partial Pass | 9/29/2022 | 9/29/2022 | 09/29/2022 |
Ron Norton | ||||
Drywall Inspection | Passed | 10/6/2022 | 10/6/2022 | 10/06/2022 |
Todd Carr | ||||
Building Final Inspection | Failed | 11/15/2022 | 11/15/2022 | 11/15/2022 |
Todd Carr | ||||
Corrections:
Building Department Corrections to be Completed
Carried Forward
11/15/2022
Patch holes in drywall ceiling in closet mechanical room, and main area has one hole, call back for a final. also mirror not installed in bathroom yet.
|
||||
Building Final Inspection | Passed | 11/18/2022 | 11/18/2022 | 11/18/2022 |
Todd Carr | ||||
Corrections:
Building Department Corrections to be Completed
Outstanding
11/15/2022
Patch holes in drywall ceiling in closet mechanical room, and main area has one hole, call back for a final. also mirror not installed in bathroom yet.
|
Condition | Status | Category |
---|---|---|
Use Tax Reconciliation | Resolved | Prior to Issuance of CO/CC |
Finance
Use Tax ReconciliationThe City of Steamboat Springs Finance department has approved a TEMPORARY CERTIFICATE (TCO/TCC) on this project. A construction use tax reconciliation is required within 90 days to be compliant with the City of Steamboat Springs Municipal Code AND before signoff for the FINAL certificate of occupancy/completion with the Routt County Building Department.
This information is sent to the email listed in City View. Please forward this information to the appropriate person to get this completed timely.
|
||
Miscellaneous Conditions | Resolved | Prior to Rough Building Wall Inspections |
Fire Prevention
Miscellaneous Conditions. Conditionally Approved –NO INSPECTIONS deferred submittal until RECEIPT of Fire Alarm/Sprinkler plan/permits by sub-contractor to Fire Prevention. See www.steamboatsprings.net, Fire and EMS Services, Fire Prevention, Downloadable Permits and Forms. NB
|
||
Miscellaneous Conditions | Resolved | Prior to Issuance of TCO/CO/CC |
Fire Prevention
Final alarm and sprinkler inspections must pass before TCO/CO sign-off.
|
Reference Number | Status | Type |
---|---|---|
SPRMH221409 | Closed | Mechanical |
SPRPL221410 | Closed | Plumbing |