Permit Application Status
SPRRN251231
| Review Type | Outcome | Est. Completion Date | Completed |
|---|---|---|---|
| COO Review - Building Code | Failed | 10/24/2025 | 10/24/2025 |
| COO Review - Fire Code | Approved | 10/28/2025 | 10/22/2025 |
| COO Review - Finance Department | Approved | 10/28/2025 | 10/21/2025 |
| Finance Department Review | Approved | 08/26/2025 | 08/25/2025 |
| Historic Preservation Review | Approved | 08/26/2025 | 08/25/2025 |
| Fire Code Review | Approved | 08/26/2025 | 08/22/2025 |
| Engineering Review | Approved | 08/26/2025 | 08/21/2025 |
| Building Code Review | Approved | 08/26/2025 | 08/21/2025 |
| Planning Review | Approved | 08/26/2025 | 08/20/2025 |
| Inspection | Outcome | Requested | Scheduled | Date Inspected |
|---|---|---|---|---|
| Framing Inspection | Passed | 9/2/2025 | 9/2/2025 | 09/02/2025 |
| Ron Norton | ||||
| Framing Inspection | Partial Pass | 9/18/2025 | 9/18/2025 | 09/18/2025 |
| Todd Carr | ||||
| Building Final Inspection | Not Ready | 10/21/2025 | 10/21/2025 | 10/21/2025 |
| Heidi Spengler | ||||
| Building Final Inspection | Partial Pass | 10/21/2025 | 10/22/2025 | 10/22/2025 |
| Todd Carr | ||||
|
Corrections:
Building Department Corrections to be Completed
Carried Forward
10/22/2025
Building Department Corrections to be Completed:
1. Please correct door that is in the far southeast office that is rubbing on the carpet currently when the door is closed, then add all door hardware in terms of strike/latch plates on door jambs that are missing.
2. Install all ceiling tiles.
3. Schedule a mechanical final inspection when you schedule the next building final, we can then review the total CFMs being delivered to the new office once the units are adjusted and balanced. This small office space at about 140 SQ FT would only need around 45 CFM.
|
||||
| Building Final Inspection | Passed | 10/24/2025 | 10/24/2025 | 10/24/2025 |
| Todd Carr | ||||
|
Corrections:
Building Department Corrections to be Completed
Resolved
10/24/2025
Building Department Corrections to be Completed:
1. Please correct door that is in the far southeast office that is rubbing on the carpet currently when the door is closed, then add all door hardware in terms of strike/latch plates on door jambs that are missing.
2. Install all ceiling tiles.
3. Schedule a mechanical final inspection when you schedule the next building final, we can then review the total CFMs being delivered to the new office once the units are adjusted and balanced. This small office space at about 140 SQ FT would only need around 45 CFM.
|
||||
| Condition | Status | Category |
|---|---|---|
| Use Tax Reconciliation | Resolved | Prior to Issuance of CO/CC |
|
Finance
Use Tax Recon work must be completed with City Finance: Contact the city directly for more information @ constructionusetax@steamboatsprings.net
|
||
| Fire Assemblies Deferred Submittal | Resolved | Prior to Rough Building Wall Inspections |
|
Fire Prevention
Conditionally Approved – NO INSPECTIONS pending submittal of Fire Alarm permits by sub-contractor to Fire Prevention. Visit www.steamboatsprings.net/Fire and EMS Services/Fire Prevention/Downloadable Permits and Forms. [Shannon Yaconiello @ 08/25/2025 3:05 PM]
|
||
| Final Fire Inspection Required | Resolved | Prior to Issuance of CO/CC |
|
Fire Prevention
Final Fire Alarm Inspection Required. [Shannon Yaconiello @ 08/25/2025 3:05 PM]
|
||
| Building Department Conditions to be Completed | Resolved | Prior to Issuance of CO/CC |
|
Building Department
Mechanical Contractor who added the supply line to the new office that was created, did not apply for a Mechanical Permit, please apply for this permit. The Final Inspection has been completed today when I did the building final, however we must have a mechanical permit applied for and issued so we can enter our results. Please email me once this permit has been issued, and I will enter the results. [Todd Carr @ 10/24/2025 11:02 AM]
|
||
| Reference Number | Status | Type |
|---|---|---|
| SPREL251323 | Closed | Electrical |
| SPRMH251720 | Closed | Mechanical |
| Date Uploaded | File Type | Name |
|---|---|---|
| Plans | ARCHITECTURAL PLAN SET 124 10TH STREET 8-14-25 (RECEIVED) (STAMPED).PDF | |
| Letter | CERTIFICATE OF COMPLETION.PDF | |
| Plans | CONSTRUCTION SITE MANAGEMENT PLAN - CENTENNIAL HALL - GRATACON (STAMPED).PDF | |
| ELECTRICAL PLANS (STAMPED).PDF | ||
| Letter | INCOMPLETE APPLICATION NOTICE.PDF | |
| Report | INSPECTION REPORT.PDF | |
| Report | INSPECTION REPORT.PDF | |
| Report | INSPECTION REPORT.PDF | |
| Report | INSPECTION REPORT.PDF | |
| Report | INSPECTION REPORT0.PDF | |
| Letter | PERMIT - DETAILED.PDF | |
| Receipt | RECEIPT.PDF | |
| Receipt | RECEIPT.PDF |