Permit Application Status
SPRRN241641
In order to view fees, you need to be signed in. You will only be able to schedule inspections if you are a contact on the permit application.
        Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.
| Review Type | Outcome | Est. Completion Date | Completed | 
|---|---|---|---|
| COO Review - Planning | TCO Approved | 09/26/2025 | 09/19/2025 | 
| 
                                                             
                                    Bob Keenan, AICP
                                    
                                 
                             | 
                        |||
| Planning has approved a TCO until 10/31/2025 so that the applicant can complete the parking lot striping, landscape plantings and interior parking lot landscape forms. | |||
| COO Review - Building Code | Approved | 09/16/2025 | 09/16/2025 | 
| 
                                                             
                                    Heidi Spengler
                                    
                                 
                             | 
                        |||
| CO approved. | |||
| COO Review - Fire Code | Approved | 09/16/2025 | 09/12/2025 | 
| 
                                                             
                                    Shannon Yaconiello
                                    
                                 
                             | 
                        |||
| All this is actually TCO review no CC. Please review again. Sprinkler final inspection passed. No alarm permit needed because the new res unit was put in so long ago that when Western Security did there upgrade it included the new unit. Ok for CC. [Shannon Yaconiello @ 09/12/2025 12:08 PM] | |||
| COO Review - Planning | Failed | 09/16/2025 | 09/09/2025 | 
| 
                                                             
                                    Jeremy Brown
                                    
                                 
                             | 
                        |||
| All this is actually TCO review no CC. Please review again. | |||
| COO Review - Finance Department | TCO Approved | 09/16/2025 | 09/09/2025 | 
| 
                                                             
                                    Denitsa Yaneva
                                    
                                 
                             | 
                        |||
| All this is actually TCO review no CC. Please review again. | |||
| COO Review - Planning | Failed | 09/02/2025 | 09/02/2025 | 
| 
                                                             
                                    Jeremy Brown
                                    
                                 
                             | 
                        |||
| COO Review - Fire Code | Failed | 09/02/2025 | 08/26/2025 | 
| 
                                                             
                                    Shannon Yaconiello
                                    
                                 
                             | 
                        |||
| Final sprinkler inspection needed before CC sign-off. [Shannon Yaconiello @ 08/26/2025 3:42 PM] | |||
| COO Review - Building Code | Failed | 08/26/2025 | 08/26/2025 | 
| 
                                                             
                                    Heidi Spengler
                                    
                                 
                             | 
                        |||
| Need to pass final electrical inspection. Not approved. | |||
| COO Review - Finance Department | Failed | 09/02/2025 | 08/26/2025 | 
| 
                                                             
                                    Denitsa Yaneva
                                    
                                 
                             | 
                        |||
| Building Code Review | Approved | 11/01/2024 | 07/14/2025 | 
| 
                                                             
                                    Todd Carr
                                    
                                 
                             | 
                        |||
| Addendum review approved due to structural conditions being different than anticipated upon walls and ceiling being opened up. | |||
| Utilities Review - City | Approved | 11/13/2024 | 11/25/2024 | 
| 
                                                             
                                    Amber Gregory
                                    
                                 
                             | 
                        |||
| 
                                         
                                            Miscellaneous
                                         
                                        Outstanding 
11/06/2024 
                                            What is the "Utility" space?
Provide original second floor for unit
                                         
                                        
                                        
                                     | 
                                |||
| 
                                         
                                            Miscellaneous
                                         
                                        Outstanding 
11/14/2024 
                                            The original plans show a toilet, shower and 2 sinks downstairs and a full living unit upstairs with 2 toilets, sinks and showers, a washing machine and kitchen.  The new plans do not show anything on the second floor.  They 
                                         
                                        
                                        
                                     | 
                                |||
| Fire Code Review | Approved | 10/25/2024 | 11/01/2024 | 
| 
                                                             
                                    Shannon Yaconiello
                                    
                                 
                             | 
                        |||
| Conditionally Approved –NO INSPECTIONS deferred submittal until RECEIPT of Fire Alarm/Sprinkler plan/permits by sub-contractor to Fire Prevention. See www.steamboatsprings.net/Fire and EMS Services/Fire Prevention/Downloadable Permits and Forms [Mike Middleton @ 10/30/2024 12:21 PM] | |||
| Planning Review | Approved | 10/25/2024 | 10/28/2024 | 
| 
                                                             
                                    Jeremy Brown
                                    
                                 
                             | 
                        |||
| Utilities Review - City | Failed | 10/25/2024 | 10/28/2024 | 
| 
                                                             
                                    Amber Gregory
                                    
                                 
                             | 
                        |||
| 
                                         
                                            Miscellaneous
                                         
                                        Carried Forward 
11/06/2024 
                                            What is the "Utility" space?
Provide original second floor for unit
                                         
                                        
                                        
                                     | 
                                |||
| Building Code Review | Approved | 10/25/2024 | 10/25/2024 | 
| 
                                                             
                                    Todd Carr
                                    
                                 
                             | 
                        |||
| Plan Review approved as submitted, we have added some conditions to this permit that should be reviewed by the applicants. | |||
| Finance Department Review | Approved | 10/25/2024 | 10/21/2024 | 
| 
                                                             
                                    Sondra Spratta
                                    
                                 
                             | 
                        |||
| Inspection | Outcome | Requested | Scheduled | Date Inspected | 
|---|---|---|---|---|
| Framing Inspection | Partial Pass | 5/14/2025 | 5/20/2025 | 05/20/2025 | 
| Silas Ebbert | ||||
| Framing Inspection | Not Ready | 7/9/2025 | 7/10/2025 | 07/10/2025 | 
| Todd Carr | ||||
| Framing Inspection | Partial Pass | 7/11/2025 | 7/14/2025 | 07/14/2025 | 
| Todd Carr | ||||
| Framing Inspection | Partial Pass | 7/21/2025 | 7/22/2025 | 07/22/2025 | 
| Todd Carr | ||||
| Drywall Inspection | Partial Pass | 7/25/2025 | 7/28/2025 | 07/28/2025 | 
| Ron Norton | ||||
| Drywall Inspection | Passed | 08/25/2025 | ||
| Todd Carr | ||||
| Building Final Inspection | Failed | 8/22/2025 | 8/25/2025 | 08/25/2025 | 
| Todd Carr | ||||
| 
                                
                                     Corrections: 
                                    
                                    Building Department Corrections to be Completed
                                 
                                Carried Forward 
08/25/2025 
All fire rated doors must have self-closing hinges activated on them, we have 4 doors at 90-minutes and 2 doors at 20-minutes that need self closing hinges activated on.  
 | 
                        ||||
| Building Final Inspection | Passed | 8/25/2025 | 8/26/2025 | 08/26/2025 | 
| Silas Ebbert | ||||
| 
                                
                                     Corrections: 
                                    
                                    Building Department Corrections to be Completed
                                 
                                Outstanding 
08/25/2025 
All fire rated doors must have self-closing hinges activated on them, we have 4 doors at 90-minutes and 2 doors at 20-minutes that need self closing hinges activated on. 
 | 
                        ||||
| Condition | Status | Category | 
|---|---|---|
| Use Tax Reconciliation | Open | Prior to Issuance of CO/CC | 
|                 
                 Finance 
Use Tax Reconciliation 
 |            
        ||
| Building Department Conditions to be Completed | Resolved | Prior to Issuance of TCO/CO/CC | 
|                 
                 Building Department 
Prior to Certificate of Occupancy being Issued, Owner/Applicant must pay all additional Fees due as a result of all new work completed that did not previously exist prior to permit issuance.
The Value of Work to be Permitted and the Total Construction Valuation are too low of values for us to accept for the amount of new construction that has taken place since the last time this unit was previously approved under issued building permits. On all of these units located at 1900-1920 Bridge Lane, the Building Department has set a cost factor for all new residential dwellings created at 1900-1920 Bridge lane, the Square Footage Cost of $100.00 per square foot for Total Construction Valuation, and $75.00 per square foot for Value of Work to be Permitted to calculate all tax fees due and permit fees due on these projects to be consistent, fair and equal to all owners of these units. For all units that have alteration work done in other areas of the Building on commercial space such as storage rooms, offices, garage space, we will use $40 per square foot for Total Project Valuation, and use $30 for Value of Work to be Permitted.
All new work that has to be performed as a result of our permitting process in terms of new products, materials, appliances, equipment, and labor to install, will be added to the above square footage cost of work done previously without permits in the past, we have added a Condition to this permit that we will not provide a Certificate of Occupancy until the owner has turned in all contracts associated with hiring professional to do the work, and invoices or receipts showing all costs of materials and products purchased. If an owner is doing their own work, then labor is calculated by taking all invoices and receipts for materials and products purchased and multiplied by two to calculate labor. The owner will then be responsible to pay these fees that are accessed to the permit at the end of the project after the contractors for services, receipts, and invoices are reviewed by the Building Department prior to Certificate of Occupancy being issued. 
Current Valuations Set on this Permit are:
Level 1 R-2 is 713 SQ FT + Level 2 R-2 at 252 SQ FT = 965 SQ FT Total
965 SQ FT x $75 = $ 72,357
965 SQ FT x $100 = $96,500 [Todd Carr @ 10/25/2024 8:04 AM] 
 
 |            
        ||
| Building Department Conditions to be Completed | Resolved | Prior to Issuance of TCO/CO/CC | 
|                 
                 Building Department 
Applicants/Owners must apply for all required Trade Permits as parent permits to the Building Permit for all work that requires Electrical, Plumbing, Mechanical, or Gas Permits. [Todd Carr @ 10/25/2024 8:09 AM]  
 |            
        ||
| Building Department Conditions to be Completed | Resolved | Prior to Rough Building Wall Inspections | 
|                 
                 Building Department 
Prior to permit issuance, applicant/owner must schedule a pre-inspection walk-through with the Building Official, to review and determine the amount of work that must be done on the project to meet the approved plans, to review what is there in terms of existing construction that is approved in it's existing condition, and what work must be done that is not approved or does not meet the approved plans at the start of the project. [Todd Carr @ 10/25/2024 8:10 AM]  
 |            
        ||
| Vested Approval Conditions | Resolved | Prior to Issuance of TCO/CO/CC | 
|                 
                 Planning Department 
Compliance with PL20240033 conditions of approval required.  
 |            
        ||
| MF/Com/I Planning CO Review | Open | Prior to Issuance of CO/CC | 
|                 
                 Planning Department 
Prior to issuance of a Temporary Certificate of Occupancy (or Certificate of Occupancy), the Department of Planning and Community Development will inspect the site to ensure the project has been built in accordance with the approved plans and the Community Development Code.  Specifically this will include inspection of parking lot striping.  Planning has approved a TCO until 10/31/2025 so that the applicant can complete the parking lot striping, landscape plantings and interior parking lot landscape forms.[Jeremy Brown @ 04/23/2025 10:26 AM] 
Site Inspection on 10/17 showed missing striping of two spaces along the Eastern property line, along with 2 missing ADA spaces.  Prior to full CO, these issues must be resolved.  [Jeremy Brown @ 10/27/2025 4:25 PM]  
 |            
        ||
| Miscellaneous Conditions | Resolved | Prior to Drywall Inspections Scheduled | 
|                 
                 Fire Prevention 
Alarm permit not needed because the new res unit was put in so long ago that when Western Security did there upgrade it included the new unit. So it's up to code. Work on level one doesn't need alarm work.
Conditionally Approved –NO INSPECTIONS deferred submittal until RECEIPT of Fire Sprinkler plan/permits by sub-contractor to Fire Prevention. See www.steamboatsprings.net/Fire and EMS Services/Fire Prevention/Downloadable Permits and Forms [Mike Middleton @ 10/30/2024 12:22 PM]  
 |            
        ||
| Final Fire Inspection Required | Resolved | Prior to Issuance of CO/CC | 
|                 
                 Fire Prevention 
Final Sprinkler Inspection Required.  [Shannon Yaconiello @ 11/01/2024 3:48 PM]  
 |            
        ||
| Miscellaneous Conditions | Open | Prior to Issuance of CO/CC | 
|                 
                 Planning Department 
Prior to issuance of a full Certificate of Occupancy, the Department of Planning and Community Development will inspect the site to ensure the project has been built in accordance with the approved plans and the Community Development Code.  Specifically this will include inspection of landscape plantings and interior parking lot landscape forms.  [Jeremy Brown @ 04/23/2025 10:27 AM]  
 |            
        ||
| Miscellaneous Conditions | Open | Prior to Issuance of CO/CC | 
|                 
                 Planning Department 
Prior to issuance of a full Certificate of Occupancy, the Department of Planning and Community Development will inspect the site to ensure the parking lot striping per the approved Development Plan for this site has been completed.   [Bob Keenan @ 09/19/2025 11:10 AM]  
 |            
        ||
| Reference Number | Status | Type | 
|---|---|---|
| SPREL251054 | Closed | Electrical | 
| SPRMH251066 | Closed | Mechanical | 