Permit Application Status
TB-21-835
In order to view fees, you need to be signed in. You will only be able to schedule inspections if you are a contact on the permit application.
Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.
Review Type | Outcome | Est. Completion Date | Completed |
---|---|---|---|
COO Review - Finance Department | Approved | 01/11/2024 | 01/04/2024 |
Sondra Spratta
|
|||
COO Review - Building Code | Approved | 10/13/2023 | 10/13/2023 |
Malea Michael-Ferrier
|
|||
COO Review - Planning | Failed | 10/13/2023 | 10/12/2023 |
Darby Kenyon
|
|||
FLC submittal required, per CDC 701. FLC submittal required prior to COO approval. | |||
COO Review - Finance Department | TCO Approved | 10/13/2023 | 10/09/2023 |
Amy Camilletti
|
|||
Planning Review | Approved | 03/31/2022 | 03/31/2022 |
Kelly Douglas, AICP
|
|||
Miscellaneous
Resolved
03/31/2022
As previously indicated, this garage does not meet duplex design standards. A Major Adjustment application must be approved by the Board of Adjustment before a garage can be placed in front of the home.
|
|||
PL20210083 Major Adjustment approved. TB-21-835 are consistent. Building permit OK. kd | |||
Building Code Review | Approved | 03/31/2022 | 03/30/2022 |
Ted Allen
|
|||
Planning Review | TCO Approved | 09/30/2021 | 10/12/2021 |
Michael Fitz
|
|||
Miscellaneous
Carried Forward
03/28/2022
As previously indicated, this garage does not meet duplex design standards. A Major Adjustment application must be approved by the Board of Adjustment before a garage can be placed in front of the home.
|
|||
Utilities Review - Mt. Werner | Approved | 09/30/2021 | 09/23/2021 |
Richard Buccino
|
|||
Engineering Review | Approved | 09/09/2021 | 09/09/2021 |
Scott Slamal
|
|||
VP legacy plan review: Steamboat Engineering Dept | |||
Planning Review | Failed | 08/26/2021 | |
Michael Fitz
|
|||
VP legacy plan review: Steamboat Planning sysadmin - Jul 13 2021 12:11PM - Principal structure setbacks (front, side, rear) OK. Overall height, average plate height, lot coverage OK. Garage overall height and average plate height OK. Resubmittal Required - setbacks appear to be shown as RN-3. This is RN-2, with a 20' principal building setback and 25' accessory building setback. Resubmittal Required - "Trash Storage Facility" shown on site plan does not show on all plans, and does not appear to meet setbacks. It is also placed within a utility easement. On some sheets it is absent and shown as a snow-storage area. Resubmittal Required - Garage (accessory building) does not meet 25' front garage setback. Resubmittal Required - all duplex design standards are met except 436.G.b regarding street-facing garages. sysadmin - Jul 26 2021 11:38AM - Per 7/26 revisions, setbacks are now depicted correctly. Garage setback now OK. "Trash storage facility" removed. Resubmittal Required - all duplex design standards are met except 436.G.b regarding street-facing garages. | |||
Building Code Review | Approved | 08/31/2021 | 08/25/2021 |
Malea Michael-Ferrier
|
|||
see TB-21-755 | |||
External Agencies Review | Approved w/ Conditions | 08/04/2021 | |
SysAdmin
|
|||
VP legacy plan review: Atmos Energy sysadmin - Aug 4 2021 8:23AM - 2# Systems will not be allowed unless proof of an appliance requiring a MINIMUM of over 7" W.C. is provided to Atmos Energy COrp for personnel review. Meter location must be approved by an Atoms Energy Corp employee during a mandatory site visit to be scheduled after foundation is in place. Meters will not be allowed under a shedding roofline or where overhanging snow is a danger to the meter set. | |||
External Agencies Review | Approved | 07/19/2021 | |
SysAdmin
|
|||
VP legacy plan review: YVEA sysadmin - Jul 19 2021 9:02AM - Meter and meter pedestal are to be located as described by YVEA. They shall not be enclosed, covered or concealed. Violation shall result in termination of service. sysadmin - Jul 19 2021 9:02AM - This approval addresses only the meter and service location. | |||
Fire Code Review | Approved | 07/15/2021 | |
SysAdmin
|
|||
VP legacy plan review: Steamboat Fire Dept | |||
Finance Department Review | Approved | 07/13/2021 | |
SysAdmin
|
|||
VP legacy plan review: Steamboat Finance Dept sysadmin - Jul 13 2021 12:10PM - See Unit A, B-21-755 for valuation and fees | |||
GIS Land Development Review | Approved | 07/13/2021 | |
SysAdmin
|
|||
VP legacy plan review: Steamboat Address sysadmin - Jul 13 2021 8:34AM - Added 1857 River Queen Lane for unit 2 of duplex |
Inspection | Outcome | Requested | Scheduled | Date Inspected |
---|---|---|---|---|
Footing Inspection | Passed | 4/11/2022 (Morning) | 4/12/2022 | 04/01/2022 |
Ron Norton | ||||
Footing Inspection | Partial Pass | 4/11/2022 | 4/12/2022 | 04/12/2022 |
Heidi Spengler | ||||
Foundation Inspection | Partial Pass | 4/21/2022 | 4/22/2022 | 04/22/2022 |
Silas Ebbert | ||||
Foundation Inspection | Not Ready | 4/25/2022 | 4/26/2022 | 04/26/2022 |
Ron Norton | ||||
Foundation Inspection | Passed | 4/28/2022 | 04/28/2022 | |
Ron Norton | ||||
Foundation Drain Inspection | Partial Pass | 05/25/2022 | ||
Ron Norton | ||||
Framing Inspection | Not Ready | 5/24/2022 | 5/25/2022 | 05/25/2022 |
Ron Norton | ||||
Rough Site Inspection | Passed | 10/28/2022 | 10/28/2022 | 10/28/2022 |
Greg Gunn | ||||
Framing Inspection | Partial Pass | 10/28/2022 | 10/28/2022 | 10/28/2022 |
Ron Norton | ||||
Foundation Drain Inspection | Passed | 10/28/2022 | 10/28/2022 | 10/28/2022 |
Ron Norton | ||||
Footing Inspection | Passed | 10/28/2022 | 10/28/2022 | 10/28/2022 |
Ron Norton | ||||
Framing Inspection | Partial Pass | 12/19/2022 | 12/19/2022 | 12/19/2022 |
Ron Norton | ||||
Framing Inspection | Failed | 4/12/2023 | 4/12/2023 | 04/12/2023 |
Jeff Yeiser | ||||
Corrections:
Building Department Corrections to be Completed
Carried Forward
04/12/2023
Building Department Corrections to be Completed
North unit, no squash blocking on north wall under rafters, four pack of 2x6 kings separating lower level window unsupported, needs to be grouted. No structurals for sauna framing.
|
||||
Framing Inspection | Partial Pass | 4/13/2023 | 4/13/2023 | 04/13/2023 |
Todd Carr | ||||
Corrections:
Building Department Corrections to be Completed
Resolved
04/13/2023
Building Department Corrections to be Completed
North unit, no squash blocking on north wall under rafters, four pack of 2x6 kings separating lower level window unsupported, needs to be grouted. No structurals for sauna framing.
|
||||
Insulation Inspection | Failed | 4/18/2023 | 04/18/2023 | |
Todd Carr | ||||
Corrections:
Building Department Corrections to be Completed
Carried Forward
04/18/2023
We cannot approve the insulation until we receive an addendum that recognizes and shows the exact R-value of the core bond foam that has been installed on all exterior walls, include all wall types in the addendum, so basement concrete walls, stick framed walls over the concrete wall on the inside, and all stick framed walls above grade, please make sure draw up all wall assemblies that have changed so we have something to review in the office and in the field to approve the changes. The sauna room must be included as well, as this is 100% core bond for roof and walls, so include this in the addendum with listed R-values based on R-7 per inch of core bond. Call back for a reinspection after the addendum is reviewed and approved.
|
||||
Building Final Inspection | Passed | 10/6/2023 | 10/6/2023 | 10/06/2023 |
Todd Carr |
Condition | Status | Category |
---|---|---|
Miscellaneous Conditions | Resolved | Prior to Issuance of CO/CC |
Finance
At the end of the project, City of Steamboat Springs Finance requires a construction use tax reconciliation be completed to be compliant with the City of Steamboat Springs Municipal Code AND prior to signoff for the FINAL certificate of occupancy/completion with the Routt County Building Department.
|
||
Miscellaneous Conditions | Resolved | |
Planning Department
At the time of project completion, request certificate of occupancy inspections from the Department of Planning and Community Development to ensure the project has been built in accordance with the approved plans and the Community Development Code. The inspection may include but is not limited to general site planning and grading, outdoor lighting, parking, retaining walls, building height and location, number of dwelling units, and consistency with approved building design.
|
||
Use Tax Reconciliation | Resolved | Prior to Issuance of CO/CC |
Sales Tax Department
Use Tax Reconciliation
|
||
FLC Submittal | Resolved | Prior to Rough Site Inspection |
Planning Department
Foundation location certificate shall be provided
|
||
SFR/Dup Planning CO Review | Resolved | Prior to Issuance of TCO/CO/CC |
Planning Department
At the time of project completion, request certificate of occupancy inspections from the Department of Planning and Community Development to ensure the project has been built in accordance with the approved plans and the Community Development Code. The inspection may include but is not limited to general site planning and grading, outdoor lighting, parking, retaining walls, building height and location, number of dwelling units, and consistency with approved building design.
|
||
Blower Door Test Results | Resolved | Prior to Certificate of Occupancy/Completion |
Building Department
Blower Door Test Results
|
Reference Number | Status | Type |
---|---|---|
SPREL231529 | Closed | Electrical |
Date Uploaded | File Type | Name |
---|---|---|
1998-001 LOT 3 EAGLES VISTA SUB ILC - FLC (1).PDF | ||
2015 IECC AIR-LEAKAGE TEST - 1857 & 1859 RIVER QUEEN LANE.PDF | ||
Plans | 202153 LANTERO- RIVER QUEEN REV4 3-18-22 (RECEIVED) (STAMPED).PDF | |
Letter | CERTIFICATE OF COMPLETION.PDF | |
FOUNDATION ADDENDUM.PDF | ||
Report | INSPECTION REPORT.PDF | |
Report | INSPECTION REPORT.PDF | |
Report | INSPECTION REPORT.PDF | |
Report | INSPECTION REPORT.PDF | |
Report | INSPECTION REPORT.PDF | |
Report | INSPECTION REPORT.PDF | |
Report | INSPECTION REPORT.PDF | |
Report | INSPECTION REPORT.PDF | |
Report | INSPECTION REPORT.PDF | |
Report | INSPECTION REPORT.PDF | |
Report | INSPECTION REPORT.PDF | |
Report | INSPECTION REPORT.PDF | |
Report | INSPECTION REPORT.PDF | |
Report | INSPECTION REPORT.PDF | |
Report | INSPECTION REPORT.PDF | |
Permit | PERMIT - DETAILED.PDF | |
Plans | STEAMBOAT_GARAGE SHEETS_11 FEBRUARY 2022 (RECEIVED) (STAMPED).PDF | |
Plans | STEAMBOAT_GARAGE TRUSSES_11 FEBRUARY 2022 (RECEIVED).PDF |