City of Steamboat Springs Web Portal

Permit Application Status

SPREL240810


In order to view fees, you need to be signed in. You will only be able to schedule inspections if you are a contact on the permit application.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

SPREL240810
Electrical
Permit(s) Issued
SERAC PINE GROVE STEAMBOAT LAND OWNER LLC
New
Electrical work associated with new construction of 4-story hotel. Scope will include new electrical service and outdoor pool
06/27/2024
06/27/2024
06/27/2027

Locations

Property
217100003

Address
1760 CENTRAL PARK DR

Permits

Permit Number: SPREL240810-EL1

Electrical
Issued

Reviews

Review Type Outcome Est. Completion Date Completed
Electrical Review Approved 07/19/2024 06/28/2024

Inspections

Inspection Outcome Requested Scheduled Date Inspected
Electrical Final Inspection Pending
Tom Cook
Corrections:


Building Department Corrections to be Completed
Outstanding
03/31/2026
1. Unit 330 undercabinet lights not installed due to drywall patch not complete. 2. Unit 333 cooktop not installed in countertop. 3. Unit 338 Pass 4. Unit 339 ADA unit. Kitchen switches not installed. Cooktop not installed in countertop. 5. Unit 340 cooktop not installed in countertop. 6. Unit 342 Pass 7. Unit 344 cooktop not installed in countertop. 8. Unit 345 cooktop not installed in countertop. 9. Unit 346 Pass 10. Unit 347 cooktop not installed in countertop. 11. Unit 348 cooktop not installed in countertop. 12. Unit 349 cooktop not installed in countertop. 13. Unit 350 cooktop not installed in countertop. 14. Unit 352 Load out room not ready for final. 15. Unit 354 cooktop not installed in countertop. 16. Unit 355 cooktop not installed in countertop. 17. Unit 356 cooktop not installed in countertop. 18. Unit 357 cooktop not installed in countertop. 19. Unit 358 cooktop not installed in countertop. 20. Unit 359 cooktop not installed in countertop. 21. Unit 360 cooktop not installed in countertop. 22. Unit 361 cooktop not installed in countertop. 23. Unit 363 Pass 24. Unit 364 cooktop not installed in countertop. Disposal receptacle requires GFCI protection. 25. Unit 365 Pass 26. Unit 369 cooktop not installed in countertop. 27. Unit 202 loadout unit not ready.

Electrical Temp Service Passed 8/6/2024 8/6/2024 08/06/2024
Dave Pieknik
Electrical Rough-in Inspection Partial Pass 8/22/2024 8/22/2024 08/22/2024
Tom Cook
Electrical Underground/Under slab Partial Pass 8/28/2024 8/28/2024 08/28/2024
Tom Cook
Electrical Underground/Under slab Passed 9/20/2024 9/20/2024 09/20/2024
Tom Cook
Electrical Rough-in Inspection Partial Pass 9/26/2024 9/26/2024 09/26/2024
Dave Pieknik
Electrical Rough-in Inspection Partial Pass 10/9/2024 10/9/2024 10/09/2024
Tom Cook
Electrical Rough-in Inspection Partial Pass 10/18/2024 10/18/2024 10/18/2024
Tom Cook
Electrical Temp Service Passed 02/05/2025
Tom Cook
Electrical Rough-in Inspection Not Ready 2/5/2025 2/5/2025 02/05/2025
Tom Cook
Electrical Rough-in Inspection Partial Pass 3/19/2025 3/19/2025 03/19/2025
Tom Cook
Electrical Rough-in Inspection Partial Pass 3/20/2025 3/20/2025 03/20/2025
Tom Cook
Electrical Rough-in Inspection Partial Pass 06/17/2025
Tom Cook
Electrical Underground/Under slab Partial Pass 07/03/2025
Tom Cook
Electrical Rough-in Inspection Failed 7/3/2025 7/3/2025 07/03/2025
Tom Cook
Electrical Underground/Under slab Partial Pass 7/17/2025 7/17/2025 07/17/2025
Tom Cook
Electrical Rough-in Inspection Partial Pass 7/17/2025 7/17/2025 07/17/2025
Tom Cook
Electrical Underground/Under slab Partial Pass 7/25/2025 7/25/2025 07/25/2025
Tom Cook
Electrical Rough-in Inspection Partial Pass 7/30/2025 7/30/2025 07/30/2025
Tom Cook
Electrical Rough-in Inspection Partial Pass 8/5/2025 8/5/2025 08/05/2025
Tom Cook
Electrical Rough-in Inspection Partial Pass 8/19/2025 8/19/2025 08/19/2025
Tom Cook
Electrical Rough-in Inspection Partial Pass 9/5/2025 9/5/2025 09/05/2025
Tom Cook
Electrical Underground/Under slab Partial Pass 9/17/2025 9/17/2025 09/17/2025
Tom Cook
Electrical Rough-in Inspection Partial Pass 9/24/2025 9/24/2025 09/24/2025
Tom Cook
Electrical Rough-in Inspection Partial Pass 10/01/2025
Tom Cook
Electrical Rough-in Inspection Partial Pass 10/3/2025 10/3/2025 10/03/2025
Tom Cook
Electrical Underground/Under slab Partial Pass 10/03/2025
Tom Cook
Electrical Underground/Under slab Partial Pass 10/03/2025
Tom Cook
Electrical Rough-in Inspection Partial Pass 10/20/2025 10/20/2025 10/20/2025
Tom Cook
Electrical Rough-in Inspection Partial Pass 10/22/2025 10/22/2025 10/22/2025
Tom Cook
Electrical Rough-in Inspection Partial Pass 10/29/2025 10/29/2025 10/29/2025
Tom Cook
Electrical Rough-in Inspection Partial Pass 11/6/2025 11/6/2025 11/06/2025
Tom Cook
Electrical Rough-in Inspection Failed 11/14/2025 11/14/2025 11/14/2025
Tom Cook
Electrical Rough-in Inspection Partial Pass 11/14/2025
Tom Cook
Electrical Underground/Under slab Partial Pass 11/14/2025 11/14/2025 11/14/2025
Tom Cook
Electrical Rough-in Inspection Failed 11/14/2025
Tom Cook
Electrical Underground/Under slab Partial Pass 11/20/2025 11/20/2025 11/20/2025
Tom Cook
Electrical Rough-in Inspection Partial Pass 11/20/2025 11/20/2025 11/20/2025
Dave Pieknik
Electrical Rough-in Inspection Partial Pass 12/2/2025 12/2/2025 12/02/2025
Tom Cook
Electrical Perm Service Passed 12/4/2025 12/4/2025 12/04/2025
Tom Cook
Electrical Rough-in Inspection Partial Pass 12/4/2025 12/4/2025 12/04/2025
Tom Cook
Electrical Rough-in Inspection Partial Pass 12/11/2025 12/11/2025 12/11/2025
Tom Cook
Electrical Rough-in Inspection Partial Pass 12/18/2025 12/18/2025 12/18/2025
Tom Cook
Electrical Rough-in Inspection Partial Pass 12/30/2025 12/30/2025 12/30/2025
Tom Cook
Electrical Rough-in Inspection Partial Pass 1/15/2026 1/15/2026 01/15/2026
Tom Cook
Electrical Rough-in Inspection Partial Pass 1/21/2026 1/21/2026 01/21/2026
Tom Cook
Electrical Rough-in Inspection Partial Pass 01/21/2026
Tom Cook
Electrical Rough-in Inspection Partial Pass 1/29/2026 1/29/2026 01/29/2026
Dave Pieknik
Electrical Rough-in Inspection Partial Pass 2/4/2026 2/4/2026 02/04/2026
Tom Cook
Electrical Rough-in Inspection Partial Pass 2/11/2026 2/11/2026 02/11/2026
Tom Cook
Electrical Rough-in Inspection Partial Pass 2/25/2026 2/25/2026 02/25/2026
Dave Pieknik
Corrections:


Building Department Corrections to be Completed
Carried Forward
02/25/2026
Small section of lobby lid was in the process of being dropped. EC had to disconnect wiring and boxes. Reschedule rough inspection when complete.

Electrical Rough-in Inspection Partial Pass 2/26/2026 2/26/2026 02/26/2026
Dave Pieknik
Corrections:


Building Department Corrections to be Completed
Carried Forward
02/26/2026
Small section of lobby lid was in the process of being dropped. EC had to disconnect wiring and boxes. Reschedule rough inspection when complete.

Electrical Rough-in Inspection Partial Pass 3/3/2026 3/3/2026 03/03/2026
Tom Cook
Corrections:


Building Department Corrections to be Completed
Carried Forward
03/03/2026
Small section of lobby lid was in the process of being dropped. EC had to disconnect wiring and boxes. Reschedule rough inspection when complete.

Electrical Rough-in Inspection Partial Pass 03/09/2026
Tom Cook
Corrections:


Building Department Corrections to be Completed
Carried Forward
03/09/2026
Small section of lobby lid was in the process of being dropped. EC had to disconnect wiring and boxes. Reschedule rough inspection when complete.

Electrical Final Inspection Partial Pass 3/9/2026 3/9/2026 03/09/2026
Tom Cook
Electrical Final Inspection Partial Pass 3/10/2026 3/10/2026 03/10/2026
Tom Cook
Electrical Perm Service Passed 3/10/2026 3/10/2026 03/10/2026
Tom Cook
Electrical Perm Service Passed 03/10/2026
Tom Cook
Electrical Final Inspection Failed 3/24/2026 3/24/2026 03/24/2026
Dave Pieknik
Corrections:


Building Department Corrections to be Completed
Carried Forward
03/24/2026
1. Unit 330 undercabinet lights not installed due to drywall patch not complete. 2. Unit 333 cooktop not installed in countertop. 3. Unit 338 Pass 4. Unit 339 ADA unit. Kitchen switches not installed. Cooktop not installed in countertop. 5. Unit 340 cooktop not installed in countertop. 6. Unit 342 Pass 7. Unit 344 cooktop not installed in countertop. 8. Unit 345 cooktop not installed in countertop. 9. Unit 346 Pass 10. Unit 347 cooktop not installed in countertop. 11. Unit 348 cooktop not installed in countertop. 12. Unit 349 cooktop not installed in countertop. 13. Unit 350 cooktop not installed in countertop. 14. Unit 352 Load out room not ready for final. 15. Unit 354 cooktop not installed in countertop. 16. Unit 355 cooktop not installed in countertop. 17. Unit 356 cooktop not installed in countertop. 18. Unit 357 cooktop not installed in countertop. 19. Unit 358 cooktop not installed in countertop. 20. Unit 359 cooktop not installed in countertop. 21. Unit 360 cooktop not installed in countertop. 22. Unit 361 cooktop not installed in countertop. 23. Unit 363 Pass 24. Unit 364 cooktop not installed in countertop. Disposal receptacle requires GFCI protection. 25. Unit 365 Pass 26. Unit 369 cooktop not installed in countertop.

Electrical Final Inspection Partial Pass 3/31/2026 3/31/2026 03/31/2026
Dave Pieknik
Corrections:


Building Department Corrections to be Completed
Carried Forward
03/31/2026
1. Unit 330 undercabinet lights not installed due to drywall patch not complete. 2. Unit 333 cooktop not installed in countertop. 3. Unit 338 Pass 4. Unit 339 ADA unit. Kitchen switches not installed. Cooktop not installed in countertop. 5. Unit 340 cooktop not installed in countertop. 6. Unit 342 Pass 7. Unit 344 cooktop not installed in countertop. 8. Unit 345 cooktop not installed in countertop. 9. Unit 346 Pass 10. Unit 347 cooktop not installed in countertop. 11. Unit 348 cooktop not installed in countertop. 12. Unit 349 cooktop not installed in countertop. 13. Unit 350 cooktop not installed in countertop. 14. Unit 352 Load out room not ready for final. 15. Unit 354 cooktop not installed in countertop. 16. Unit 355 cooktop not installed in countertop. 17. Unit 356 cooktop not installed in countertop. 18. Unit 357 cooktop not installed in countertop. 19. Unit 358 cooktop not installed in countertop. 20. Unit 359 cooktop not installed in countertop. 21. Unit 360 cooktop not installed in countertop. 22. Unit 361 cooktop not installed in countertop. 23. Unit 363 Pass 24. Unit 364 cooktop not installed in countertop. Disposal receptacle requires GFCI protection. 25. Unit 365 Pass 26. Unit 369 cooktop not installed in countertop. 27. Unit 202 loadout unit not ready.

Conditions

There are no conditions for this permit application, or you are not authorized to view them.

Related Permit & Planning Applications

Reference Number Status Type
SPRNR240188 Permit(s) Issued New Commercial Building
SPRPL241239 Permit(s) Issued Plumbing
SPRPO251164 Permit(s) Issued Pool/Hot Tub
SPRMH251500 Permit(s) Issued Mechanical
SPRPL251590 Permit(s) Issued Plumbing
SPRMH260105 Permit(s) Issued Mechanical

Documents & Images

Date Uploaded File Type Name
Report INSPECTION REPORT.PDF
Report INSPECTION REPORT.PDF
Report INSPECTION REPORT.PDF
Report INSPECTION REPORT.PDF
Report INSPECTION REPORT.PDF
Report INSPECTION REPORT.PDF
Report INSPECTION REPORT.PDF
Report INSPECTION REPORT.PDF
Report INSPECTION REPORT.PDF
Report INSPECTION REPORT.PDF
Report INSPECTION REPORT.PDF
Report INSPECTION REPORT.PDF
Report INSPECTION REPORT.PDF
Report INSPECTION REPORT.PDF
Report INSPECTION REPORT.PDF
Report INSPECTION REPORT.PDF
Report INSPECTION REPORT.PDF
Report INSPECTION REPORT.PDF
Report INSPECTION REPORT.PDF
Report INSPECTION REPORT.PDF
Report INSPECTION REPORT.PDF
Report INSPECTION REPORT.PDF
Report INSPECTION REPORT.PDF
Report INSPECTION REPORT.PDF
Report INSPECTION REPORT.PDF
Report INSPECTION REPORT.PDF
Report INSPECTION REPORT.PDF
Report INSPECTION REPORT.PDF
Report INSPECTION REPORT.PDF
Report INSPECTION REPORT.PDF
Report INSPECTION REPORT.PDF
Report INSPECTION REPORT.PDF
Report INSPECTION REPORT.PDF
Report INSPECTION REPORT.PDF
Report INSPECTION REPORT.PDF
Report INSPECTION REPORT.PDF
Report INSPECTION REPORT.PDF
Report INSPECTION REPORT.PDF
Report INSPECTION REPORT.PDF
Report INSPECTION REPORT.PDF
Report INSPECTION REPORT.PDF
Report INSPECTION REPORT.PDF
Report INSPECTION REPORT.PDF
Report INSPECTION REPORT.PDF
Report INSPECTION REPORT.PDF
Report INSPECTION REPORT.PDF
Report INSPECTION REPORT.PDF
Report INSPECTION REPORT.PDF
Report INSPECTION REPORT.PDF
Report INSPECTION REPORT.PDF
Report INSPECTION REPORT.PDF
Report INSPECTION REPORT.PDF
Report INSPECTION REPORT1.PDF
Report INSPECTION REPORT2.PDF
Report INSPECTION REPORT3.PDF
Report INSPECTION REPORT4.PDF
Report INSPECTION REPORT5.PDF
Report INSPECTION REPORT6.PDF
Letter PERMIT - DETAILED.PDF